FAQ n° 19453

Produits obsolètes
Analyseurs de puissances, d'énergies, de pertubations

Question
Asked on 6/23/19

Hello,

I changed my computer, and since I can not connect my two CA8332B and CA8334B devices to the software, the two devices are not recognized on the computer. I am using a RS232 optical cord DB9F (supplied with the device) and a RS232 adapter - USB HX0055 under Windows 10. Do you have a solution for me?

Response
Answered on 6/24/19

It is indeed a driver compatibility problem of the HX0055 adapter and the operating system  Windows 10, so I advise you to connect directly via an RS232 connection, or to order the replacement of the HX0055 adapter, with the reference HX0055B, and which solves this problem.