Product presentation

All the parameters simultaneously

Designed for test and maintenance teams working in industrial or administrative buildings, the Qualistar+ CA 8336 can be used to obtain a snapshot of the main features characterizing the quality of the electrical network. This analyser's functions make it the ideal instrument for preventive or corrective maintenance. It can also be used to perform a complete energy survey of an installation. For sizing installations or troubleshooting switching faults, the CA 8336 is equipped with Inrush and TrueInrush functions. Easy to handle and particularly compact, this instrument also offers a large number of calculated values and several processing functions. The CA 8336 is equipped with 4 voltage measurement channels and 4 current measurement channels. The CA 8336 captures and records all the parameters, transients, alarms and waveforms simultaneously. When current sensors are connected to the CA 8336, it recognizes them automatically. It also offers the possibility of mixing different types of current sensors and configuration of the ratios allows direct reading of the measurements.

Specially designed for work in the field:

  • Direct access to the main functions (configuration, etc.)
  • Direct access to the measurements (harmonics, flicker, etc.)
  • Voltage/current inputs equipped with colour-coded inserts
  • Large colour TFT screen for easy reading
  • Battery life: 10 hrs

The multiple functions of the Qualistar+ C.A 8336 make it a versatile instrument. It is suitable for applications up to 1,000 V in CAT III and 600 V in CAT IV. Software The measurements obtained with the Qualistar models can be processed using two software tools: PAT2 delivered as standard and Dataview®, available as an option. They allow configuration, transfers, processing and analysis. In addition, Dataview® offers the possibility of generating reports according to the voltage quality standards.

Specific accessories

  • The ESSAILEC cable can be used to carry out tests without disturbing or interrupting the power supply circuit on the meters and the protection relays installed in the secondary circuits of current or voltage transformers.
  • Reeling Box This practical magnetized winder equipped with the MultifFIX system allows you to adjust the length of your cables. It can be opened so that users can install banana-type leads for voltage measurements or MiniFlex® MA193-250 flexible sensors for current measurements. It also provides a simple means of stowing your cables.
  • PA31ER adapter This enables self-powering of the Qualistar+ via the phase from 100 V to 1,000 V, AC or DC. It is connected directly to the voltage inputs and is:
  • All the Qualistar+ models are delivered with a set of rings/inserts for quick identification and customization of the colour coding for each country.

Large choice of current sensors for current measurements from 5 mA to 10 kA

To view the documents available in other languages

Electrical safety

Electrical safety

Electrical safety

Electrical safety

Software

Software

Guarantee

Guarantee

Actual effective measurement

Actual effective measurement

Load start measurement

Load start measurement

USB communication mode

USB communication mode

Need information about our solutions? Our experts are available to advise and assist you with your project. Contact a sales representative now for a detailed presentation and an offer tailored to your needs.


Contact a sales representative

Highlights

  • All the measurements you need in one box
  • Proven ease of use
  • A recorder of gargantuan length
  • Alarms on events down to half a period
  • Captures transients as short as a few µs
  • Load start mode with waveform display

Features

Number of channels

4U / 4I

Number of inputs

5V / 4I

IEC 61000-4-30

Reports EN50160 Ed02

Voltage (TRMS AC+DC)

2 V to 1,000 V

Voltage ratio

up to 500 kV

C193

1 A to 1,000 Aac

AmpFLEX® or MiniFlex

100 mA to 10,000 Aac

PAC93

1 A to 1,300 Aac/dc

E3N/E27

50 mA to 100 Aac/dc

J93

50 A to 3,500 Aac / 50 A to 5,000 Adc

Current ratio

Up to 60 kA

Frequency

40 Hz to 69 Hz

Powers

W (P), VA (S), var (Q1, N, D), PF, DPF, cos ϕ;, tan ϕ;

Energies

Wh, varh (Q1h, Nh, Dh), VAh

Harmonics

Yes

THD

Yes, from rank 0 to 50, phase

Expert Mode

Yes

Transients

210

Flicker

Pst and Plt

Inrush Mode

Yes > 10 minutes

Imbalance

Yes

Alarms

10,000 of 40 different types

Peak

Yes

Vector representation

Automatic

Display

TFT color screen ¼ VGA 320 x 240 diagonal 148 mm

Screen & curve capture

50

Electrical safety

IEC 61010 1,000 V CAT III / 600 V CAT IV

Protection index

IP53 / IK08

Languages

More than 27

Communication interface

USB

Autonomy

Up to 10 hours

Power supply

Rechargeable battery 9.6 V NiMH or mains power supply

Dimensions / Weight

240 x 180 x 55 mm / 1.9 kg

Documentation and support

Do you have a question about using or installing your measurement equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.


Contact support

Do you have a question about using or installing your measurement equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.


Contact support

The PAT software allows you to control single-phase wattmeters and energy analysers, as well as clamp meters.

The PAT software is a tool that enables you to:

  • Configure the devices,
  • Download and view data stored in memory,
  • Take instantaneous readings,
  • Display data in tabular or graphical form,
  • Export this measurement data to DataView (*.dvb files) or to a spreadsheet.

For the CA 8220/8230, CA 8332/32B/34/34B, CA 8335/8435 (embedded software versions v3.x) and F407/F607, use PAT. The main updates to PAT are:

  • Various bug fixes.

The PAT 2 software enables you to control single-phase wattmeters and energy analysers, as well as clamp meters.

The PAT 2 software is a tool that enables you to:

  • Configure the devices,
  • Download and view data stored in memory,
  • Take instantaneous readings,
  • Display data in tabular or graphical form,
  • Export this measurement data to DataView (*.dvb files) or to a spreadsheet.

For the CA 8331/33/36, CA 8436 and CA 8335 (embedded software version v4.x), use PAT 2. The main updates in PAT 2 are:

  • Addition of a Bulgarian translation
  • Various bug fixes.
The Qualistar+ & CA 8230 Recording Duration Calculator
Available in French and English, this tool allows you to simulate the possible recording duration of QualistarPlus devices.
The user selects the device and the parameters they wish to record, as well as the acquisition interval.
The possible recording duration, based on an empty memory, and the end date are automatically calculated and displayed.

The devices covered are:

  • CA 8336
  • CA 8436
  • CA 8333
  • CA 8331
  • CA 8335

==> From version v4.x onwards

  • CA 8230

Some information on the devices’ other storage capacities (alarms, snapshots, etc.) is also displayed.

Download Microsoft .NET Framework 4, which is required to run the Trend Duration Calculator.

USB - Serial adapter ((USB-RS232)

  • Driver for HX0055 compatible with Windows 7
  • Driver for HX0055B compatible with Windows 7 / 8.1 /10 /11

Firmware for Qualistar Plus CA 8331, CA 8333,  CA 8336 & CA 8436 network analysers.

To download the firmware, click on the link below and refer to the "read-me first.txt" file included. This firmware upgrade is compatible with all previous hardware versions.       

Do you have a question about using or installing your measurement equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.


Contact support

References and accessories

To fully meet your expectations, a range of accessories is available that is compatible with your equipment. Feel free to add them to your quote request to obtain a complete and tailored solution.

CA 8336 Voltage quality analyser 4U-4I

CA 8336 Voltage quality analyser 4U-4I

P01160591

Graphic analyser of power, energy, harmonics and three-phase disturbances (4I/4U) CA8336 - EN50160 campaigns

picto

MN93A AC current clamp

P01120434B

AC current clamp - 2 current ranges 5mA to 100A - 20 mm clamping diameter - For Qualistar and PEL power recorders

picto

MN93 AC current clamp

P01120425B

AC current clamp - Current range 500mA to 200A - Clamping diameter 20 mm - For Qualistar and PEL power loggers

picto

A193-450 AmpFlex

P01120526B

Flexible AC current sensor - Current range 100mA to 10000A - Diameter 140mm - For Qualistar and PEL power loggers

picto

A193-800 AmpFlex

P01120531B

Flexible AC current transducer - Current range 100mA to 10000A - Diameter 250mm - For Qualistar and PEL power loggers

picto

PAC93 AC/DC current clamp

P01120079B

AC-DC current clamp - 1A to 1000A current range - 39 mm clamping diameter - For CA82xx - CA833x - CA 843x - PEL power loggers

picto

C193 AC current clamp

P01120323B

AC current clamp - Current range 1A to 1000A - Clamping diameter 52 mm - For Qualistar and PEL power loggers

picto

Current measurement accessory for Qualistar and PEL

P01101959

5A current adaptor for TI output 3-phase banana plugs for Qualistar QualistarPlus and Qualistar2 CA833x & CA834x and PEL

picto

Current measurement accessory for Qualistar and PEL

P01102131

ESSAILEC-type adapter box for current inputs for CA82xx - CA833x - CA843x - PEL10x - PEL11x power analysers and recorders

picto

Storage and carrying case

P01298055

Storage bag No21

picto

Storage and carrying case

P01298056

Carrying bag No22 to protect and store your equipment and associated accessories - 355 x 255 x 235 mm - QualistarPlus accessories

picto

DataView Software

P01102095

PC software for configuring, saving and processing data, editing reports, etc. for Chauvin Arnoux measuring instruments

picto

Protection accessory

P01102059

Anti-scratch protective film for the screen of QualistarPlus CA8335 - CA8331 - CA8333 - CA8336 - CA8435 - CA8436 (spare)

picto

Configuration accessory

P01102080

Set of plastic pins and rings in 12 colours to identify leads, current sensors and device inputs

picto

Mains adapter

P01102057

PA30W mains adaptor for powering QualistarPlus CA8331 - CA8333 - CA8335 - CA8336 - CA6116N and PEL115 (office use)

picto

Communication cable

P01295293

Communication cable with USB type A connector to USB type B

picto

Measuring and test tip(s)

P01103058Z

Set of 2 magnetic test points (for voltage measurement only) / Test point diameter: 6.6 mm / D4 mm angled female plug / 4 A / 1000 V CAT III - 600 V CAT IV

picto

Measurement leads

P01295476

Set of 4 x 3m cords - 4mm straight Banana-Banana - 4 crocodile clips - set of colour-coded marker pins

picto

Test leads

P01295483

Set of 5 cords of 3m - Banana-Banana straight 4mm - 5 crocodile clips - set of colour-coded markers

picto

Connection adapter

P01102081

Adapter for E3N and E27 current clamps for QualistarPlus series power analysers and PEL102 - 103 - 104 recorders

picto

J93 AC/DC current clamp

P01120110

AC-DC current clamp - Current range 50-3500 Aac - 50-5000 Adc for CA833x - CA843x - PEL10x

picto

Instrument battery

P01296024

Replacement rechargeable battery - 4 Ah Ni-MH technology - For QualistarPlus CA8335 - CA8331 - CA8333 - CA8336 - CA8435 - CA8436

picto

Mechanical accessory

P01102149

Reeling Box storage accessory for tangle-free voltage cables. Integrated magnet for easy attachment to any metal surface.

picto

12V cigarette-lighter power supply converter

HX0061

Voltage converter from 10-60V DC 4A cigarette-lighter socket to 2P+T 120-150V DC 32W max female connector

picto

Mains power adapter

P01102150

PA31ER mains adapter for powering QualistarPlus CA8335 - CA8331 - CA8333 - CA8336 voltage measurement channels.

picto

RS232-USB adapter

HX0055B

9-pin USB-RS232 adapter for PC, Windows Vista/7/8/10 and MAC compatible, 1.8 m long, 1Mbps speed, RTS/CTS flow control

picto

MA194-350 MiniFlex

P01120592

Flexible AC current sensor - Current range 100mA to 10000A - Diameter 100mm - For Qualistar and PEL power loggers

picto

MA194-250 MiniFlex

P01120593

Flexible AC current transducer - Current range 100mA to 10000A - Diameter 70mm - For Qualistar and PEL power loggers

picto

MA194-1000 MiniFlex

P01120594

Flexible AC current transducer - Current range 100mA to 10000A - Diameter 300mm - For Qualistar and PEL power loggers

picto

E27 Isolated AC/DC current probe for scope

P01120027

Isolated 100A AC/DC 100 kHz current probe for oscilloscope. Ø11.8 mm cable gland. Sensitivity 100-10 mV / 1A. Powered by battery or external 5V. 600V CAT III/300V CAT IV.

picto

Mains adapter

P01101967

Mains adapter 230V 50/60 Hz European plug 2P for PAC series AC/DC current meters

picto

E94 AC/DC current clamp

P01120044

AC-DC current clamp - Current range 100mA 100A - 2 ratings 10A and 100A - Clamping diameter 11.8 mm - For Qualistar2 and PEL power recorders

picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto

Add one or more products to your quote request in just a few clicks. Our teams will analyze your needs and get back to you quickly with a personalized offer tailored to your requirements.