Product presentation

Complete and lightweight, the C.A 6131 multifunction tester can be used to perform all the measurements and tests needed by certification organizations and maintenance teams to qualify an electrical installation.

Ergonomics

The C.A 6131 is simple to use. On the front panel, each key corresponds to a function. It is designed for simplified use in all conditions:

  • Stand for positioning on a bench or table
  • 4-point strap for effortless hands-free use
  • Backlit screen for easy reading, even when the lighting is insufficient
  • Terminal strip with explicit markings (L, N, PE, +, com) to prevent connection errors
  • Remote-control probe for starting tests remotely
  • A three-pole cable for direct measurements on 2P + E sockets Measurements

The C.A 6131 can be used for voltage, continuity, resistance, insulation and loop measurements. The current can be measured with an external clamp. It is possible to test type A & AC RCDs in ramp or pulse mode. The C.A 6131 also checks the phase rotation. For greater efficiency, the C.A 6131 provides an immediate visual indication of the test result (OK/NOK).

Main technical specifications:

  • Voltage measurement: 550 VAC / 800 VDC
  • Continuity at 200 mA,
  • Resistance from 1 to 99.99 kΩ
  • Insulation: 250V and 500V test voltage, measurement up to 999 MΩ
  • Zs (Z L-PE) loop without tripping: 1 to 2,000 Ω, calculation of Ik
  • Zs (Z L-PE) high-current loop with tripping and Zi (Z L-N or Z L-L), from 0.1 to 400 Ω, calculation of Ik
  • Type AC & A RCDs: 30mA, 100mA, 300 mA, 500 mA, 650 mA
  • RCD in pulse mode: tripping time
  • RCD in ramp mode (30 mA): tripping current
  • Phase rotation: 45 to 550V; 45 to 65 Hz
Electrical safety

Electrical safety

Protection class

Protection class

Need information about our solutions? Our experts are available to advise and assist you with your project. Contact a sales representative now for a detailed presentation and an offer tailored to your needs.


Contact a sales representative

Highlights

  • Earth measurement by loop methods
  • Continuity measurement at 0.2A
  • Insulation testing
  • RCD testing: current and trip time

Features

Continuity

Range / Resolution / Accuracy

0.00 to 9.99 Ω / Compensation of leads up to 5 Ω; I >= 200 mA / 0.01 Ω / ± (2 % L + 2 pt)

Resistance

Range / Resolution / Accuracy

1 to 9,999 Ω —; 10.00 to 99.99 kΩ / 1 Ω —; 10 Ω / ± (1 % L + 5 pt)

Insulation

Test voltage

250 V / 500 V

Range / Resolution / Accuracy

0.01 to 999.9 MΩ / 10 kΩ or 100 kΩ / ± (3 % L + 3 pt)

Earth resistance - 3P method

Range

-

Resolution

-

Accuracy

-

Measurement frequency

-

Loop measurement (Zi)

Connection type

By banana plugs

Range / Resolution / Accuracy

Measurement current 300 mA; 0.1 to 399.9 Ω / 0.1 Ω / ± (5%L + 2 pt)

Ik calculation

1 to 9,999 A

Differential test

Installation voltage

90 to 450 V; 45 to 65 Hz

Types and calibers

AC and A; 30 mA - 100 mA - 300 mA - 500 mA - 650 mA

Trigger time

0.5 x I DN; 1 x I DN; 5 x I DN / 5.0 to 300 ms

Trigger current

30 mA: -0 .. +(7%L +3.3% I DN + 2 mA)

Fault voltage: Range / resolution / accuracy

1.0 to 25.0 V —; 25.0 to 70.0 V / 0.1 V / ± (15% L + 3 pt) —; ± (5% L + 2 pt)

Automatic test sequence

No

Voltage & Frequency

Voltage: Range / Resolution / Accuracy

2.0 to 550.0 VAC / 0.1 V / ± (1%L+2pt); 0.0 to 800.0 VDC / 0.1 V / ± (1%L+2pt)

Frequency: Range / Resolution / Accuracy

-

Phase rotation

45 to 550 V / 45 to 65 Hz

AUX sensor function (CA 6131)

AC+DC range: Range / Resolution / Accuracy

2.0 to 999.9 mV —; 1.000 to 1.2000 V / 0.1 mV —; 1 mV / ±(1 % L + 2 pt)

DC range / Resolution / Accuracy

±(0.0 to 999.9 mV) —; ±(1.000 to 2.000 V) / 0.1 mV —; 1 mV / ±(1 % L + 2 pt)

General characteristics

Display

LCD 231 segments with blue backlight

Memory

-

Communication

-

Software

-

Power supply

6 x LR 6 or AA batteries

Autonomy

> 1900 continuity measurements at 1 Ω

Dimensions / Weight

223 x 126 x 70 mm / approximately 1.1 kg

Environment

Usage: 0 to 40 °C / Storage: -10 to 70 °C (HR 80%)

Protection

IP 54 (IEC 60529); IK 04 (IEC 50102)

Standards / Electrical safety

EMC: IEC 61326-1; IEC 61010-1; IEC 61010-2-030; IEC 61010-2-034, 600V CAT III, 300V CAT II on charger input

IEC 61557 compliance

Parts 1, 2, 3, 4, 6, 7 and 10

Documentation and support

Do you have a question about using or installing your measurement equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.


Contact support

Language *

Do you have a question about using or installing your measurement equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.


Contact support

Reading before install for Firmware update for CA 6131 / CA 6133 / MX 535

A loader for updating the firmware of the CA 6131, CA 6133 and MX535 installation controllers.

Do you have a question about using or installing your measurement equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.


Contact support

References and accessories

To fully meet your expectations, a range of accessories is available that is compatible with your equipment. Feel free to add them to your quote request to obtain a complete and tailored solution.

CA 6131 Installation controller EU version

CA 6131 Installation controller EU version

P01146011

Multifunction installation tester, voltage, loop and Ik calculation, continuity, resistance, insulation, DDR A and AC test, phase rotation, mV sensor, 6 LR6 batteries, carry bag and leads.

picto

Remote control sensor No. 4 - MX535-CA6131 and CA 6133

P01102157

No. 4 remote control probe for use with MX535, CA 6131 and CA 6133 low-voltage installation controllers

picto

90 cm continuity rod, protection max. 1 kV

P01102084A

Continuity probe / insulated female socket D4 mm / length 90 cm (3 x 30 cm) / protection 1000V max.

picto

15m earth kit - red/yellow/green cables

P01102019

Earth kit comprising a flexible bag with 2 18 cm stakes, 1 red 15 m cable on H reel, 1 yellow 10 m cable on H reel, 1 green 5 m cable on H reel.

picto

3P earth kit, 50m, poles, coils and mallet

P01102021

Earthing kit comprising a carry bag with 2 T-pegs, 1 reel of 50 m red cable, 1 reel of 50 m blue cable, 1 reel of 10 m green cable, 1 mallet, 5 D4 mm terminal/stick adapters.

picto

MN73 AC leakage current clamp

P01120421

200A AC current clamp for leakage current testing. Ø20mm insert. Output signal: V AC. S/E ratio: 1000 mV-10 mV/A AC. Output via cord and Ø4mm insulated male plugs.

picto

Test lead for MX535, CA 6131, CA 6133

HX0300

Tripod test lead / Euro plug for MX535, CA 6131 and CA 6133 multifunction installation controllers

picto

Neck strap for MX535, CA 6131 and CA 6133

HX0302

Neck strap for hands-free use of MX535, CA6131 and CA6133 low-voltage installation controllers

picto

Measuring and testing tip(s)

P01295454Z

Set of 2 moulded test probes (1 red / 1 black) for CAT III & IV 1000V installations

picto

Measurement and test accessory(ies)

P01295457Z

Set of 2 alligator clips (1 red and 1 black) 15A for CAT III & IV 1000V installations

picto

Alkaline battery(ies)

P01296033

1.5V cylindrical battery, LR6, AA, RC6 format, alkaline technology, supplied individually

picto

Measuring and test leads

P01295451Z

Set of 2 moulded PVC cables (1 red, 1 black) / Ø4mm insulated straight male plug - Ø4mm insulated angled male plug / 15A / 1.5 m / 1000V CAT IV

picto

Green test probe 1000V CAT IV Banana 4 mm

P01101920A

1000V CAT IV green touch probe for use with multifunction installation controllers and machine controllers

picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto
picto

Add one or more products to your quote request in just a few clicks. Our teams will analyze your needs and get back to you quickly with a personalized offer tailored to your requirements.