MX535 Installation tester EU version
Multifunction installation tester, voltage, earth spike - loop and Ik calculation, continuity, resistance, insulation, DDR A and AC test, phase rotation, 6 Acu NiMH, USB recharge
Complete and lightweight, the C.A 6131 multifunction tester can be used to perform all the measurements and tests needed by certification organizations and maintenance teams to qualify an electrical installation.
Ergonomics
The C.A 6131 is simple to use. On the front panel, each key corresponds to a function. It is designed for simplified use in all conditions:
The C.A 6131 can be used for voltage, continuity, resistance, insulation and loop measurements. The current can be measured with an external clamp. It is possible to test type A & AC RCDs in ramp or pulse mode. The C.A 6131 also checks the phase rotation. For greater efficiency, the C.A 6131 provides an immediate visual indication of the test result (OK/NOK).
Main technical specifications:
Electrical safety
Protection class
Need information about our solutions? Our experts are available to advise and assist you with your project. Contact a sales representative now for a detailed presentation and an offer tailored to your needs.
Range / Resolution / Accuracy
0.00 to 9.99 Ω / Compensation of leads up to 5 Ω; I >= 200 mA / 0.01 Ω / ± (2 % L + 2 pt)
Range / Resolution / Accuracy
1 to 9,999 Ω —; 10.00 to 99.99 kΩ / 1 Ω —; 10 Ω / ± (1 % L + 5 pt)
Test voltage
250 V / 500 V
Range / Resolution / Accuracy
0.01 to 999.9 MΩ / 10 kΩ or 100 kΩ / ± (3 % L + 3 pt)
Range
-
Resolution
-
Accuracy
-
Measurement frequency
-
Connection type
By banana plugs
Range / Resolution / Accuracy
Measurement current 300 mA; 0.1 to 399.9 Ω / 0.1 Ω / ± (5%L + 2 pt)
Ik calculation
1 to 9,999 A
Installation voltage
90 to 450 V; 45 to 65 Hz
Types and calibers
AC and A; 30 mA - 100 mA - 300 mA - 500 mA - 650 mA
Trigger time
0.5 x I DN; 1 x I DN; 5 x I DN / 5.0 to 300 ms
Trigger current
30 mA: -0 .. +(7%L +3.3% I DN + 2 mA)
Fault voltage: Range / resolution / accuracy
1.0 to 25.0 V —; 25.0 to 70.0 V / 0.1 V / ± (15% L + 3 pt) —; ± (5% L + 2 pt)
Automatic test sequence
No
Voltage: Range / Resolution / Accuracy
2.0 to 550.0 VAC / 0.1 V / ± (1%L+2pt); 0.0 to 800.0 VDC / 0.1 V / ± (1%L+2pt)
Frequency: Range / Resolution / Accuracy
-
Phase rotation
45 to 550 V / 45 to 65 Hz
AC+DC range: Range / Resolution / Accuracy
2.0 to 999.9 mV —; 1.000 to 1.2000 V / 0.1 mV —; 1 mV / ±(1 % L + 2 pt)
DC range / Resolution / Accuracy
±(0.0 to 999.9 mV) —; ±(1.000 to 2.000 V) / 0.1 mV —; 1 mV / ±(1 % L + 2 pt)
Display
LCD 231 segments with blue backlight
Memory
-
Communication
-
Software
-
Power supply
6 x LR 6 or AA batteries
Autonomy
> 1900 continuity measurements at 1 Ω
Dimensions / Weight
223 x 126 x 70 mm / approximately 1.1 kg
Environment
Usage: 0 to 40 °C / Storage: -10 to 70 °C (HR 80%)
Protection
IP 54 (IEC 60529); IK 04 (IEC 50102)
Standards / Electrical safety
EMC: IEC 61326-1; IEC 61010-1; IEC 61010-2-030; IEC 61010-2-034, 600V CAT III, 300V CAT II on charger input
IEC 61557 compliance
Parts 1, 2, 3, 4, 6, 7 and 10
Language *
Do you have a question about using or installing your measurement equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.
Language *
Do you have a question about using or installing your measurement equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.
Reading before install for Firmware update for CA 6131 / CA 6133 / MX 535
A loader for updating the firmware of the CA 6131, CA 6133 and MX535 installation controllers.
Do you have a question about using or installing your measurement equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.
To fully meet your expectations, a range of accessories is available that is compatible with your equipment. Feel free to add them to your quote request to obtain a complete and tailored solution.
P01146011
Multifunction installation tester, voltage, loop and Ik calculation, continuity, resistance, insulation, DDR A and AC test, phase rotation, mV sensor, 6 LR6 batteries, carry bag and leads.
P01102157
No. 4 remote control probe for use with MX535, CA 6131 and CA 6133 low-voltage installation controllers
P01102084A
Continuity probe / insulated female socket D4 mm / length 90 cm (3 x 30 cm) / protection 1000V max.
P01102019
Earth kit comprising a flexible bag with 2 18 cm stakes, 1 red 15 m cable on H reel, 1 yellow 10 m cable on H reel, 1 green 5 m cable on H reel.
P01102021
Earthing kit comprising a carry bag with 2 T-pegs, 1 reel of 50 m red cable, 1 reel of 50 m blue cable, 1 reel of 10 m green cable, 1 mallet, 5 D4 mm terminal/stick adapters.
P01120421
200A AC current clamp for leakage current testing. Ø20mm insert. Output signal: V AC. S/E ratio: 1000 mV-10 mV/A AC. Output via cord and Ø4mm insulated male plugs.
HX0300
Tripod test lead / Euro plug for MX535, CA 6131 and CA 6133 multifunction installation controllers
HX0302
Neck strap for hands-free use of MX535, CA6131 and CA6133 low-voltage installation controllers
P01295454Z
Set of 2 moulded test probes (1 red / 1 black) for CAT III & IV 1000V installations
P01295457Z
Set of 2 alligator clips (1 red and 1 black) 15A for CAT III & IV 1000V installations
P01296033
1.5V cylindrical battery, LR6, AA, RC6 format, alkaline technology, supplied individually
P01295451Z
Set of 2 moulded PVC cables (1 red, 1 black) / Ø4mm insulated straight male plug - Ø4mm insulated angled male plug / 15A / 1.5 m / 1000V CAT IV
P01101920A
1000V CAT IV green touch probe for use with multifunction installation controllers and machine controllers
Add one or more products to your quote request in just a few clicks. Our teams will analyze your needs and get back to you quickly with a personalized offer tailored to your requirements.